ICF-1280I Series
Technology Standard: IEC 61158-2 for PROFIBUS DP Interface P1/P2 Ports: ST Fiber P3 Port: PROFIBUS DP (DB9 female) Relay Alarm: One relay output, current carrying capacity 2 A @ 30 VDC, normally open
Technology Standard: IEC 61158-2 for PROFIBUS DP Interface P1/P2 Ports: ST Fiber P3 Port: PROFIBUS DP (DB9 female) Relay Alarm: One relay output, current carrying capacity 2 A @ 30 VDC, normally open
LED Indicators
| PWR1, PWR2, Ready, P1, P2, P3, Fault DIP Switches: DIP 1 ~ 4: Baud rate setting DIP 5: Fiber link monitor DIP 6 to 7: Linear/Star mode (w/ optional P1/P2 disable), Redundant Ring mode DIP 8: Remote Fiber Diagnosis PROFIBUS Communication Transmission Rate: 9.6, 19.2, 45.45, 93.75, 187.5, 500, 1500, 3000, 6000, and 12000 Kbps Auto Baudrate: Yes Isolation Protection: 2 kV Fiber Point-to-point, line (bus), star, and redundant ring topologies |
Mechanical Characteristics
| Housing | Metal Mounting: DIN-rail mounting, wall mounting (optional accessories) Dimensions: 39 x 115 x 70 mm (1.54 x 4.53 x 2.76 in) Weight: 225 g |
|---|
Operating Environment
| Operating Temperature | Standard model: 0 ~ 60 โ (32 ~ 140 ยฐF) Wide temp model: -40 ~ 75 โ (-40 ~ 167 ยฐF) Storage Temperature: -40 ~ 75 โ (-40 ~ 167 ยฐF) Relative Humidity: 5 ~ 95% (non-condensing) |
|---|
Power Requirements
| Input Voltage | 12 ~ 48 VDC Connection Type: Terminal block Power Line Protection: Level 3 (2 kV) Surge Protection Overcurrent Protection: 1.1 A |
|---|
Safety Certifications
| Safety | UL 508, EN 60950-1 EMC: CE, FCC Part 15 Subpart B |
|---|
Software, Firmware & Drivers
| File Name | Type | Version | Operating System | Release Date |
|---|---|---|---|---|
| ICF-1280I-series-firmware-v4.1.rom | Firmware | v4.1 | โ | 2024-06-26 |
| ICF-1280I-series-mib-package-v4.1.zip | Software Package | v4.1 | โ | 2024-06-26 |
| ICF-1280I-series-eds-package-v1.0.zip | Software Package | v1.0 | โ | 2024-04-24 |
Support Documents
| File Name | Type | Version | Release Date |
|---|
Related Content
๐
Application Guide
Building future-proof industrial network infrastructure
๐ฅ
Video
Witness the evolution of industrial networking with Moxa
๐
Application Note
Enhance network performance for IP surveillance systems
๐
Solution Brief
Strengthen network resilience for industrial control systems
Need Help Choosing the Right Product?
Contact our engineering team for detailed specifications, pricing, and availability.